Online Inverters
Inverter Range: 300 VA,600 VA ,1 KVA and more. BE SERVO SYSTEM Power Inverter is based on PWM, MOSFET Technology as well as conventional components are mounted to ensure reliable quality, compact size and easy serviceability. Inverter shuts down automatically if exposed to excessive load and keeps on beeping and sensing the load to switch itself on to find the load within the specified limits, eliminating the need of manual resetting the users. If the load is more than 115% of the rated capacity it will shut and protect itself. This Process will happen till the extra load is there. To overcome close the extra load.
Technical Specifications
Capacity |
600 VA
– 3 kva |
Model/Make |
Branded |
Technology |
SPWM,
IGBT/MOSFET (for more than 72 DC volt IGBT preferred) |
Input
Voltage |
230 V
AC, Single phase |
Input
Voltage Range |
160 V
AC TO 270 V AC |
Input
Frequency Range |
45 TO
55 Hz |
Input
Over Voltage Protection |
280 V
AC |
Input
Under Voltage Protection |
155 V
AC |
Over
Voltage Cut Off |
Should
be offered externally |
Output
Voltage |
230 V
AC Single Phase +-1% |
Frequency |
50 HZ
+-1% |
Load
Power Factor |
0.8 Lag
to Unity |
Isolation |
Output
load be isolated through a transformer of same rating |
Output
Over Voltage Protection |
245 V
AC Single Phase |
Output Under
Voltage Protection |
210 V
AC Single Phase |
Over
Load Capacity |
125% of
rated load for 60 sec |
Short
Circuit Protection |
Soft
shut down should occur without blowing any fuse |
Isolation |
Manual
Bypass Switch Should be provided of same rating |
Indicators |
1) Over
Temperature- Required |
Static
Switch |
Automatic
Bi-directional should take care of 100% uninterrupted transfer of load from
UPS Transfer Time 85 % Inverter Efficiency > 90 % |
Metering |
Separate/Single
Digital Meter |
Battery
Period of Backup |
Sealed
Maintenance Free Lead Acid Battery of >= 12 V each of uniform AH rating |
DC Bus
Ripple |
2 Hr
with 100% load < 1% |
Battery
Recharge Time |
From
Fully Discharge Condition To 100% Charged Condition< 12 hrs Total Dc Bus
Banks SINGLE |
Battery
Housing |
Closed
housing with suitable lockers |
Auditable
Alarm for Following Conditions |
•
Battery Low |
Environmental |
•
Operating Temperature < 45 DegreeCelsius |